Low voltage capacitor banks
Medium voltage range capacitor banks
- Insultation class : 0,66 kV (tested at 2,5 kV 50 Hz for 1 minute)
- Built-in power supply for auxiliary circuits
- Connector block for built-in-load-shedding contact
- Protective circuit breaker fitted - wired
- Fixed step
- Summing current transformer
The following is required :
- Power cables in accordance with table
- A current transformer to be positioned in phase L3 of the installation upstream of all the receivers and the capacitor bank:
Primary : according to the installation
Secondary : 5 A
Power : 10 VA (recommended) - class 1